netBooter B Series PDU – Overview
The netBooter B Series is an entry-level switched PDU designed for simple local network power management. It provides individual outlet control, AutoPing-based recovery, and serial console access, making it ideal for budget-conscious deployments that require basic remote reboot capabilities without advanced security, monitoring, or enterprise management features.
Key Features
Individual Outlet Control
- Independently switch each outlet on or off.
- Remotely reboot connected devices through a local network connection or serial interface.
AutoPing Recovery
- Monitors devices via ICMP ping.
- Automatically power cycles outlets when a monitored device becomes unresponsive.
- Can send email notifications when failures occur.
Local Network Management
- Built-in HTTP web interface for outlet control.
- Simple setup and operation for small deployments.
Serial Console Access
- Available with:
- USB (FTDI-based)
- DB9 RS-232
- Supports local management and automation integration.
Typical Applications
Small Equipment Installations
- Cable modems
- Routers
- Media players
- Network gateways
Budget-Conscious Deployments
- Cost-sensitive projects
- Basic remote reboot requirements
- Simple scheduling and power cycling
Manufacturing & Industrial Use
- Equipment restart automation
- Production bench testing
- Firmware update power cycling
- Machine control applications
Technical Specifications
Input Power
| Parameter | Specification |
|---|
| Input Connector | IEC 320 C14 |
| Voltage | 100–120 VAC, 60 Hz or 100–240 VAC, 50–60 Hz |
| Maximum Current | 15 A (12 A derated) |
| Phase | Single Phase |
| Input Metering | None |
Output Power
| Parameter | Specification |
|---|
| Outlet Voltage | 100–120 VAC or 100–240 VAC |
| Outlet Types | NEMA 5-15R or IEC 320 C13 |
| Outlet Count | 2 or 5 |
| Outlet Switching | Individual outlet control |
| Outlet Metering | None |
| Overload Protection | None |
Networking & Communication
Supported Protocols
- HTTP
- SMTP
- Telnet
- DHCP
- NTP
- BootP
Network Interface
- 10 Base-T Half Duplex Ethernet (RJ45)
Security
| Feature | Available |
|---|
| HTTPS | ✖ |
| SSH | ✖ |
| SNMP | ✖ |
| LDAP | ✖ |
| RADIUS | ✖ |
| Encryption | ✖ |
User Management
- Up to 3 local user accounts
- Password protection
Serial Interfaces
Front Panel Features
- Individual outlet status LEDs
- PDU power status LED
- Network activity LED
Unlike DU and DX models, the B Series does not include an inlet current display.
Environmental Monitoring
| Feature | Support |
|---|
| Temperature Monitoring | ✖ |
| Humidity Monitoring | ✖ |
| Sensor Ports | ✖ |
The B Series does not support environmental sensors.
Physical Specifications
| Form Factor | Outlet Count |
|---|
| Compact | 2 |
| 1U Strip | 5 |
Dimensions
| Model | Dimensions |
|---|
| Compact | 6.2″ × 5.4″ × 1.75″ |
| 1U Strip | 19″ × 2.125″ × 1.75″ |
Environmental Ratings
- Operating Temperature: -5°C to 60°C
- Storage Temperature: -25°C to 65°C
- Humidity: 5–95% RH (non-condensing)
Available Models
Compact (2 Outlet)
| SKU | Voltage | Outlet Type | Serial |
|---|
| NP-02B-USB | 120V | NEMA 5-15R | USB |
| NP-02B-DB9 | 120V | NEMA 5-15R | DB9 |
| NP-02BH-USB | 240V | IEC C13 | USB |
| NP-02BH-DB9 | 240V | IEC C13 | DB9 |
1U Strip (5 Outlet)
| SKU | Voltage | Outlet Type | Serial |
|---|
| NP-05B-USB | 120V | NEMA 5-15R | USB |
| NP-05B-DB9 | 120V | NEMA 5-15R | DB9 |
| NP-05BH-USB | 240V | IEC C13 | USB |
| NP-05BH-DB9 | 240V | IEC C13 | DB9 |
Comparison of netBooter Product Families
| Feature | B Series | DU Series | DX Series | SP Series |
|---|
| Individual Outlet Control | ✔ | ✔ | ✔ | ✔ |
| AutoPing Recovery | ✔ | ✔ | ✔ | ✔ |
| HTTP Access | ✔ | ✔ | ✔ | ✔ |
| HTTPS Access | ✖ | ✔ | ✔ | ✔ |
| SSH Access | ✖ | ✖ | ✔ | ✔ |
| SNMP Support | ✖ | v1/v2 | v1/v2/v3 | v1/v2/v3 |
| VLAN Support | ✖ | ✖ | ✔ | ✔ |
| LDAP/RADIUS | ✖ | ✖ | ✔ | ✔ |
| Central Management Portal | ✖ | ✖ | ✔ | ✔ |
| Current Monitoring | ✖ | ✔ | ✔ | ✔ |
| Environmental Sensors | ✖ | Temperature | Temp/Humidity | Advanced Sensors |
| Outlet Power Metering | ✖ | ✖ | ✖ | ✔ |
| Energy Metering (kWh, PF, VA) | ✖ | ✖ | ✖ | ✔ |
| ATS Models | ✖ | ✖ | ✖ | ✔ |
| Three-Phase Models | ✖ | ✖ | ✖ | ✔ |
| Maximum Outlet Count | 5 | 20 | 5 | 36 |
Product Positioning
B Series
- Basic local network power control
- Lowest-cost solution
- Small equipment groups
- Local or serial access only
DU Series
- Secure remote power control
- Current monitoring
- Temperature monitoring
- Larger outlet counts
DX Series
- Enterprise remote power management
- VLAN support
- Centralized cloud management
- Zero-touch deployment
SP Series
- Data center-grade intelligent PDU
- Outlet-level metering
- Energy analytics
- ATS redundancy
- Three-phase power options
- Large-scale infrastructure deployments
The B Series is best suited for organizations that need simple, economical outlet control and automatic reboot functionality without the advanced networking, security, monitoring, and power analytics capabilities found in the DU, DX, and SP Series.